How to calculate home inverter or UPS backup time
When the power goes, two numbers matter: how many watts you are actually drawing, and how much energy is sitting in the battery. Everything else — “1 kVA inverter”, “150 Ah tubular”, “lithium 24 V” — is a way of talking about those two numbers. This calculator turns the ratings on the battery sticker into an estimated runtime, and, if you type a target number of hours, into the amp-hours you would need.
The watt-hour formula
Battery energy in watt-hours is:
Nominal Wh = Ah × voltage × number of batteries
Not all of that energy is usable. The inverter wastes some of it as heat (efficiency, often around 80–90%). A lead-acid battery should not be taken to empty if you care about its life (depth of discharge). So:
Usable Wh = nominal Wh × (efficiency ÷ 100) × (DoD ÷ 100)
Backup hours = usable Wh ÷ load in watts
A published worked example, reproduced here
Take a 24 V, 9 Ah UPS battery, a 300 W load, 85% inverter efficiency and 80% usable depth (a lithium-like depth, used here so the arithmetic is easy to check):
- Nominal energy = 24 × 9 = 216 Wh
- Usable energy = 216 × 0.85 × 0.80 = 146.88 Wh
- Runtime = 146.88 ÷ 300 = 0.4896 hours ≈ 29 minutes
Switch this form to 24 V, 9 Ah, 80% depth, 85% efficiency and 300 W and you should see the same half hour. That is the check used in the tests for this page. A typical Indian home tubular battery is larger — 150 Ah at 12 V is 1,800 Wh nominal — but the method does not change.
Lead-acid versus lithium
Most home inverters in India still use a tubular lead-acid battery. Planning at about 50% depth of discharge is a conservative habit: it leaves margin for age and for the high-current drop in capacity that lead-acid shows when you pull a heavy load. Lithium iron phosphate banks can usually be planned closer to 80%. If your installer gave you a different figure, pick Custom and type it. Do not assume a five-year-old tubular battery still holds its rated Ah.
Building a realistic load
Add the watts of everything that will stay on during the cut. The chips on this page use typical running watts, not starting surges: a ceiling fan about 75 W, an LED bulb 10 W, a router 12 W, a 40-inch LED television around 80 W, a fridge perhaps 150 W on average (more when the compressor starts). A 1.5-ton air conditioner is usually hundreds to more than a thousand watts and will dominate any small home inverter — if you plan to run one, size both the inverter and the battery for that load honestly, or leave it off.
The optional inverter VA suggestion is (watts ÷ 0.8 power factor) × 1.25. It is a starting point so you do not pair a 400 W load with a 600 VA unit and then add a fridge motor. Confirm against the manufacturer’s chart.
How to use the “desired hours” box
If you want two hours of backup for a 300 W essential load on a 12 V tubular bank at 50% DoD and 85% efficiency, the tool will also show the amp-hours that implies. Compare that with the Ah already printed on your battery. If the estimate is shorter than you need, you can lower the load (fewer fans, LED instead of older lamps) or add battery capacity — not just buy a higher VA inverter. A bigger inverter without a bigger battery will not store more energy.
All of the arithmetic stays in this browser. There is no live electricity-tariff or weather feed, and no product to sell you. Use the result as a plan, then test it once with a known load and a clock — that measured runtime is the number that finally matters.